- Simple and easy to set
- Precise control performance and high dynamic response
- Pressure regulator built in to eliminate variations in supply air pressure
- Low air consumption due to piezo electric microvalve
- Input/ output signal isolated
- Simple conversion to direct acting (DA)or reverse acting(RA)
- Single and double acting available
- No hunting on the small actuators
- 1/2 split range available
- Position transmitter and limit switches to be built in one unit
- High resistance against shock and vibration
 
- Position transmitter(4...20mA output signal)
- Limit switches (open and close at any two points)
- Gauge block with two stainless steel pressure gauges
- Explosion proof type (Exd ¥±B T6,Exia ¥±C T6)
SEL
SER
Linear Type
Rotary Type
Single
Double
Single
Double
Input Signal
4...20mA, 2-wire
Split Range Application
8.5V DC @ 20mA (425§¤)
Voltage Supply Min./Max.
3.6mA / 50mA
Characteristic
1.4...7.0bar(20...100psi) / filtered compressed dry and non-oiled air
Stroke | Angle
5..80mm (max. up to 150mm) 40...90¢ª (max.up to 100¢ª)
Air Supply Pressure
1.4...7.0bar(20...100psi) / filtered compressed dry and non-oiled air
Air Consumption
0.08§©/h at 1.4 bar input pressure
Output Pressure Range 0...100% supply air pressure
Linearity Within ¡¾ 0.5% F.S
Hysteresis Within ¡¾ 0.2% F.S
Sensitivity Within ¡¾ 0.1% F.S
Operating Temperature -20¡É ...+70¡É
Pneumatic Connections Rc 1/4 or NPT 1/4
Electrical Connections G 1/2 or NPT 1/2
Body Material Aluminum diecast
Protection Class IP66, Intrinsic Safety (Exia), Flameproof (Exd)
Weight 2.3kg / with pressure gauge block
 
¨ç Mount the positioner to the control as shown below
¨è Connect the feedback lever to control valve stem at position where the angle between the valve stem and the feedback lever becomes 90¢ª as shown below when the input signal is to 12mA (50%)
¨é Stroke range for the best performance should be 5~80mm and the operating angle of the feedback lever should be maximum 45¢ª to carry out accuracy perfectly
¨ç Mount the multi-tupe barcket to the actuator as shown below
¨è Confirm the rotating direction of the actuator for air piping (see catalog and manual for details)
¨é Confirm if the feedback lever shaft "A" is placed in the orifice of the fork lever "B" and they are in perfect alignment with a rotary actuator output shaft
 
 
Confirm the rotating direction of the actuator and connect the air lines as below
  Spring Return Double Acting
Reverse Acting Out1:piped, Out2:plugged Out1:piped to Actuator port A, Out2:piped to Actuator port B
Direct Acting Out1: plugged, Out2: piped Out1:piped to Actuator port B, Out2:piped to Actuator port A
 
Description
Code
Description
Code
Actuator Operation:
L: Linear Type
R: Rotary Type
Pressure Gauge Block:
N: None
1: 6bar (90psi)
2: 10bar (150psi)
Protection Class:
F: Flameproof(Exd ¥±B T6)
I: Intrinsic Safety(Exia ¥±B T6)
W: Weatherproof to IP 66
Position Feedback :
N: None
O: Position Transmitter
(4~20mA Output Signal)
L: Two Alarm Limits
M: O+L
Feedback Lever:
£ªLinear Type


£ªRotary Type
A: Stroke (5~40 mm)
B: Stroke (5~80 mm)
C: Stroke (up to 150 mm)

F: Fork Lever (standard)
N: NAMUR Shaft (direct mounting)
Mounting Bracket :
N: None
L: DIN/IEC534(for SEL)
R: DIN VDI/VDE3845
(for SER)
 
¨ç Supply 4mA input signal and set Zero by turning the zero screw on the control board until Zero reaches 0% of the valve / actuator
¨è Supply 20mA input signal and set Span by turning the span screw on the control board until Span reaches 100% of the valve / actuator
 
Input signal should be porvided for measurement of output signal.
¨ç With a mA loop calibrator Select Measurement mode and connect £« to 4 and £­ to 5
¨è With a mulitimeter tester(mA)