- Auto-Calibration for optimum conditions
- Precise control performance and high dynamic response
- Easy operation with four key pads and full text graphical LCD
- Single and double acting
- Low air consumption due to piezo electric microvalve
- Pressure regulator built-in to eliminate variations in supply air pressure
- Problem-free characteristics on a very small actuator
- High resistance against shock and vibration
- Mounting on linear actuators according to IEC 534
- Mounting on rotary actuators according to VDI / VDE 3845 |
| |
 |
- Position transmitter (4...20mA output signal)
- Two alarm limits (Min., Max.)
- Gauge block with two stainless steel pressure gauges
- Remote-transmitter cable ( 3,5,10m)
- HART communication (FSK) |
|
 |
|
|
RSSL |
RSSR |
Linear Type |
Rotary Type |
Single |
Double |
Single |
Double |
Input Signal |
4...20mA, 2-wire |
Voltage Drop |
8.5V DC @ 20mA (425§¤) |
Min./Max. Current |
3.6mA / 50mA |
Air Supply Pressure |
1.4...7.0bar(20...100psi) / filtered compressed dry and non-oiled air |
Output Pressure |
0...100% supply air pressure / single or double action |
Shut-Off Value |
Range 0...5% of position signal |
Air Consumption |
0.08N§© / h at 1.4bar (20psi) supply |
| Hummidity Limits |
<90% RH,non-condensing |
| Stroke | Angle |
5..80mm (max. up to 150mm) |
40...90¢ª(max.up to 100¢ª) |
| Adjusted Speed |
Range 1...200 (Low 1, High 200) |
| LCD Indication |
4-digit LCD indicator |
| Scan Time |
2§Á |
| Valve Action |
Position 0...100% / Direct action (DA) / Reverse action(RA) |
| Characteristic Curve |
Linear, equal percentage 1:25 of 1:50
Linearity <=0.3% F.S / Sensitivity <=0.2% F.S / Hysteresis <=0.2% F.S |
| Temperature Limits |
Operation : -20...70¡É |
| Protection Class |
IP66 |
| Case Material |
Aluminum diecast |
| Electrical Connections |
2¡¿G 1/2 or NPT 1/2 |
| Pneumatic Connections |
Rc 14 or NPT 1/4 |
| Weight (without cable) |
2.3kg / with pressure gauge block |
|
| |
 |
 |
|
 |

¨ç Mount a Remote-transmitter RT-100 to the control valve as shown below
¨è Connect the feedback lever to the control valve stem at position where the angle between the valve stem and the feedback lever becomes 90¡Æ as shown below when the input signal is set to 12mA(50%)
¨é Stroke range for the best performance should be 5~80mm and the operating angle of the feedback lever should be maximum 45¡Æ to carry out accuracy and linearity perfectly |
 |
 |
 |
|
 |
 |
|

¨ç Mount the multi-type bracket to the actuator as shown below
¨è Confirm the rotating direction of the actuator for air piping (see catalog and manual for details)
¨é Confirm if the feedback lever shaft "A" is placed in the orifice of the fork lever "B" and they are in perfect alignment with a rotary actuator output shaft |
 |
 |
 |
|
 |
 |
| |
 |
| |
| Parameters |
Descriptions |
Functions |
Initial value |
| INPU |
Input signal |
4...20mA or 20...4mA |
4-20 mA |
| SPAN |
Span range |
0...100% span adjustment |
100% |
| ZERO |
Zero-up |
Position Zero up and down 0...99% |
0% |
| R/DA |
RA/DA |
Reverse or direct acting |
RA |
| L/E.Q |
Linear/E.Q% |
Linear, E,Q%(1:25 or 1:50) |
Linear |
| SPLT |
Split range |
4...12mA or 12...20mA |
4-20mA |
| SHUT |
Shut-off |
Valve shut off at 0...5% |
0% |
| P-GN |
P-Gain |
Proportional gain value |
Auto setting |
| I-GN |
I-Gain |
Integral gain value |
Auto setting |
| D-GN |
D-Gain |
Differential gain value |
Auto setting |
| ALAM |
Alam limit low,high |
AL1L /AL1H,AL2L /AL2H |
0-10%,90-100% |
| SPED |
Speed control |
1...200 |
200 |
| DIGN |
Display Digit |
Move to one or two decimal places |
1 |
|
| |
 |
¨ç Push MODE key for more than 5 seconds, and Auto Calibration will start.
¨è The time required for this process may be different according to the actuator volume, but it generally takes about 2~3 minutes. |
 |
| |
 |
 |
| |
 |
Note that the input signal should be provided for measurement of output signal.
¨ç With a mA loop calibrator Select Measurement mode and connect £« to 4 and £ to 5
¨è With a mulitimeter tester(mA)
|
 |
| ZERO / SPAN of position feedback will be automatically set after Auto Calibration . |
| |
 |
 |
|
Note that the alarm limits were already set at the factory to 0 ...10%for AL1(L,H) and 90...100%forAL2(L,H). Please refer to the manual for details. |
| |
 |
 |
| Description |
Code |
Description |
Code |
| Actuator Operation: |
L: Linear Type
R: Rotary Type |
Pressure Gauge Block: |
N: None
1: 6bar (90psi)
2: 10bar (150psi) |
Protection Class:
|
F: Flameproof(Exd ¥±B T6)
I: Intrinsic Safety(Exia ¥±B T6)
W: Weatherproof to IP 66 |
| Position Feedback : |
N: None
O: Position Transmitter
(4~20mA Output Signal)
L: Two Alarm Limits
M: O+L |
Feedback Lever:
Linear Type
Rotary Type |
A: Stroke (5~40 mm)
B: Stroke (5~80 mm)
C: Stroke (up to 150 mm)
F: Fork Lever (standard)
N: Namur Shaft (direct mounting) |
| HART Communicatoin: |
N: None
H: HART Comm |
| Mounting Bracket : |
N: None
L: DIN/IEC534(for SSL)
R: DIN VDI/VDE3845(for SSR) |
|
| |
 |
| unit : mm |
 |
 |