- Auto-Calibration for optimum conditions
- Precise control performance and high dynamic response
- Easy operation with four key pads and full text graphical LCD
- Single and double acting actuators
- Low air consumption due to electric microvalve
- Pressure regulator built in to eliminate variations in supply air pressure
- Problem-free characteristics on very small actuator
- Economical energy saving
- Extremely Vibration Resistant Design
- High resistance against shock and vibration
- Mounting on linear actuators according to IEC 534
- Mounting on rotary actuators according to VDI / VDE 3845
 
- Position transmitter (4...20mA output signal)
- Two alarm limits (Min., Max)
- Gauge block with two stainless pressure gauges
- Explosion proof type (Exd ¥±B T6,Exia ¥±C T6)
- HART communication (FSK)
SSL
SSR
Linear Type
Rotary Type
Single
Double
Single
Double
Input Signal
4...20mA, 2-wire
Voltage Drop
8.5V DC @ 20mA (425§¤)
Min./Max. Current
3.6mA / 50mA
Air Supply Pressure
1.4...7.0bar(20...100psi) / filtered compressed dry and non-oiled air
Output Pressure
0...100% supply air pressure / single or double action
Shut-Off Value
Range 0...5% of position signal
Air Consumption
0.08N§© / h at 1.4bar (20psi) supply
Hummidity Limits <90% RH,non-condensing
Stroke | Angle 5..80mm (max. up to 150mm) 40...90¢ª(max.up to 100¢ª)
Adjusted Speed Range 1...200 (Low 1, High 200)
LCD Indication 4-digit LCD indicator
Scan Time 2§Á
Valve Action Position 0...100% / Direct action (DA) / Reverse action (RA)
Characteristic Curve Linearity <= 0.3% F.S/ Sensitivity <= 0.2% F.S/ Hysteresis<=0.2% F.S
Temperature Limits Operation : -20...70¡É
Protection Class IP66, Intrinsic Safety (Exia), Flameproof (Exd)
Case Material Aluminum diecast
Electrical Connections 2¡¿G 1/2 or NPT 1/2
Pneumatic Connections Rc 14 or NPT 1/4
Weight 2.3kg / with pressure gauge block
 

¨ç Mount the positioner to the control as shown below
¨è Connect the feedback lever to control valve stem at position where the angle between the valve stem and the feedback lever becomes 90¢ª as shown below when the input signal is to 12mA (50%)
¨é Stroke range for the best performance should be 5~80mm and the operating angle of the feedback lever should be maximum 45¢ª to carry out accuracy perfectly

¨ç Mount the multi-tupe barcket to the actuator as shown below
¨è Confirm the rotating direction of the actuator for air piping (see catalog and manual for details)
¨é Confirm if the feedback lever shaft "A" is placed in the orifice of the fork lever "B" and they are in perfect alignment with a rotary actuator output shaft
Confirm the rotating direction of the actuator and connect the air lines as shown below
 
  Spring Return Double Acting
Reverse Acting Out1:piped, Out2:plugged Out1:piped to Actuator port A, Out2:piped to Actuator port B
Direct Acting Out1: plugged, Out2: piped Out1:piped to Actuator port A, Out2:piped to Actuator port B
 
 
 
 
Parameters Descriptions Functions Initial value
INPU Input signal 4...20mA or 20...4mA 4-20 mA
SPAN Span range 0...100% span adjustment 100%
ZERO Zero-up Position Zero up and down 0...99% 0%
R/DA RA/DA Reverse or direct acting RA
L/E.Q Linear/E.Q% Linear, E,Q%(1:25 or 1:50) Linear
SPLT Split range 4...12mA or 12...20mA 4-20mA
SHUT Shut-off Valve shut off at 0...5% 0%
P-GN P-Gain Proportional gain value Auto setting
I-GN I-Gain Integral gain value Auto setting
D-GN D-Gain Differential gain value Auto setting
ALAM Alam limit low,high AL1L /AL1H,AL2L /AL2H 0-10%,90-100%
SPED Speed control 1...200 200
DIGN Display Digit Move to one or two decimal places 1
 
¨ç Push MODE key for more than 5 seconds, and Auto Calibration will start
¨è The time required for this process may be different according to actuator volume, but it generally takes about 2~3 minutes
 
 
Note that input signal should be provided for measurement of output signal.
¨ç With a mA loop calibrator Select Measurement mode and connect £« to 4 and £­ to 5
¨è With a mulitimeter tester(mA)
ZERO / SPAN of position feedback will be automatically set after Auto Calibration .
 
Note that the alarm limits were already set at the factory to 0...10%for AL1(L,H)and 90...100%forAL2(L,H). Please refer to the manual for details.
 
Description Code Description Code
Actuator Operation: L: Linear Type
R: Rotary Type
Pressure Gauge Block: N: None
1: 6bar (90psi)
2: 10bar (150psi)
Protection Class:
F: Flameproof(Exd ¥±B T6)
I: Intrinsic Safety(Exia ¥±B T6)
W: Weatherproof to IP 66
Position Feedback : N: None
O: Position Transmitter
(4~20mA Output Signal)
L: Two Alarm Limits
M: O+L
Feedback Lever:
Linear Type


Rotary Type
A: Stroke (5~40 mm)
B: Stroke (5~80 mm)
C: Stroke (up to 150 mm)

F: Fork Lever (standard)
N: Namur Shaft (direct mounting)
HART Communicatoin: N: None
H: HART Comm
Mounting Bracket : N: None
L: DIN/IEC534(for SSL)
R: DIN VDI/VDE3845(for SSR)
 
unit : mm
unit : mm
 
unit : mm